Featuring true on-line operation with pure sine wave output, zero transfer time to battery and complete UPS replacement capability with no downtime, the SU6000RT4U provides the highest level of protection available for mission-critical equipment from power outages, voltage fluctuations and transient surges. It converts incoming AC power to DC, and re-converts it back to filtered AC output with a pure sine wave, isolating connected components from all power problems. The SU6000RT4U has a 6kVA/4200W capacity, NEMA L14-30P 4-wire split-phase input and 12 total AC outlets (8 5-15/20R; 2 L6-20R; 2 L6-30R).With its detachable PDU, the SU6000RT4U is easily hot-swappable by a user of any skill set-no need for lengthy and expensive service calls, and no downtime if a repair or battery replacement is needed. In bypass mode, the PDU passes power to equipment without the use of the power and battery modules, allowing them to be removed while keeping your application in operation. UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The SU6000RT4U's runtime can be expanded with optional external battery packs.The SU6000RT4U features a highly efficient (94%) economy mode setting that can significantly reduce a facility's energy costs by minimizing heat output, reducing cooling requirements and consuming less electricity.An LCD display with LED indicators enables IT personnel to monitor operating modes and conditions. The LCD/LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various conditions.The SU6000RT4U features a USB port and a DB9 port that, when used with Tripp Lite's included PowerAlert software, provide comprehensive network power monitoring and control. An optional SNMPWEBCARD accessory can enable the UPS to operate as an IP managed device.The unit requires only 4U of rack space in a standard rack enclosure and can be installed in a 2-post rack using the 2POSTRMKITHD accessory, or in a tower configuration with the 2-9USTAND accessory.The SU6000RT4U comes with $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only) for connected equipment and a 2-year warranty.
- General Information
- Manufacturer
- Tripp Lite by Eaton
- Manufacturer Website Address
- https://tripplite.eaton.com/
- Brand Name
- Tripp Lite by Eaton
- Product Line
- SmartOnline
- Product Type
- Double Conversion Online UPS
- Warranty
- Limited Warranty
- 2 Year
- Technical Information
- Plug/Connector Type
- NEMA L14-30P
- Receptacle Type
- NEMA 5-15/20R
- NEMA L6-30R
- NEMA L6-20R
- Receptacle Detail
- 2 x NEMA 5-15/20R
- 8 x NEMA L6-30R
- 2 x NEMA L6-20R
- Bypass Switch
- Automatic & Manual
- Emergency Power OFF
- Yes
- Transfer Time
- 0 ns
- Power Description
- Load Capacity (VA)
- 6000 VA
- Load Capacity (Watt)
- 4200 W
- Input Voltage
- 120 V AC
- 240 V AC
- Output Voltage
- 120 V AC
- 208 V AC
- 240 V AC
- Management
- Network Management
- SNMP Manageable
- Interfaces/Ports
- USB
- Yes
- Battery Information
- Backup/Run Time (Full Load)
- 8 Minute
- Backup/Run Time (Half Load)
- 20 Minute
- Hot Swappable
- Yes
- Physical Characteristics
- Rack Height
- 4U
- Form Factor
- Tower
- Miscellaneous
- Package Contents
- SmartOnline 6000VA Rack-mountable Tower
- SU6000RT4U UPS System (with SUPDMB56 detachable PDU module)
- USB, DB9 and EPO cabling
- Rackmount installation kit for 4 post rack enclosures
- Owner's manual and warranty information
- Additional Information
Typical Applications:
Ideal for protection of sensitive electronics in any application calling for upright tower or 19-inch rackmount UPS protection. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems.Switches:
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads.Low voltage transfer to battery power:
Maintains continuous operation during undervoltages as low as 65V (L1-N:L2-N). Below this point, output is maintained utilizing battery reserves.High voltage transfer to battery power:
Maintains continuous operation during overvoltages to 140V (L1-N:L2-N). Above this point, output is maintained utilizing battery reserves.Cold Start:
Yes, inverter can be "cold started" to enable temporary AC output during a power failure.
- Software Included
- PowerAlert UPS
- Country of Origin
- China